Description
The zone monitor unit (CZMU352) connects a zone of suitable Cooper conventional detectors and a separate zone of Cooper conventional callpoints (if required).
Product Description/ Features/ Specifications
An extensive range of interfaces are available to support the Cooper range of control panels, providing solutions for most design requirements.
The zone monitor unit (CZMU352) connects a zone of suitable Cooper conventional detectors and a separate zone of Cooper conventional callpoints (if required).
Features
- Soft addressed
- Integral short circuit isolator
- Single address
- Accepts a zone of Cooper conventional detectors
- Input monitored for open, short circuit and earth contact faults
Benefits
- Quick and simple to install
- No hard addressing required (Plug and play)
- Easy to expand a system using existing wiring
Code | CZMU352 |
---|---|
Description | Zone Monitor Unit |
Standards | EN54 Pt17 & Pt18 2005 |
Specification | |
Operating Voltage | 18V dc to 30V dc |
Quiescent Current | 2.8mA |
Alarm Current | 8mA |
Current with 20 Detectors | 3.4mA |
Detector Load | 20 detectors per zone (max) |
Callpoint Load | Unlimited |
Environmental | |
Operating Temperature | -10°C to +60°C |
Humidity (Non Condensing) | 0 to 95% RH |
Physical | |
Construction | PC/ABS |
Dimensions (HxWxD) | 88mm x 147mm x 60mm |
Weight | 0.23kg |
Ingress Protection | IP40 |
Compatibility | |
Suitable for use with | Cooper Intelligent Addressable Fire Systems |