The 4 way sounder controller unit (CSC354CPR) adds functionality to your addressable panel by powering up to 4 lines of conventional output devices. The CSC354CPR gives access to Eaton’s extensive range of conventional devices, including EN54-23 certified VADs, beacons, signboards, bells and sounders.
It is ideal in situations where there is a requirement for devices with a high current draw or where conventional sounder circuits are in a remote location away from the fire alarm control panel.
This unit only uses a single address yet each circuit can be independently controlled according to the required cause and effect programming.
- Soft addressed
- Integral short circuit isolator
- Single address
- 4 Separate sounder circuit outputs (total 1.6A max)
- Avoids the need to wire conventional sounders back to the control panel
- Outputs are independently programmable (delays on circuit 1 only)
- Integral battery and power supply
- Quick and simple to install
- No hard addressing required (Plug and play)
- Increased system integrity
- Beacons and strobes can be wired direct to the
- interface (saving on both time and installation)
Code | CSC354CPR |
---|---|
Description | 4 Way Sounder Controller Unit |
Standards | CE CPR – EN54-2, EN54-4, EN54:17 |
Power Supply Unit | |
Operating Voltage | 230V ac |
Current | 0.5A |
Frequency | 50Hz |
Output | 18.5V – 29.5V |
Loop | |
Operating Voltage | 230V ac |
Current | 0.5A |
Frequency | 50Hz |
Output | 18.5V – 29.5V |
Sounder Circuit (4 of) | |
Operating Voltage | 24V |
Load per Channel | 0.8A |
Alarm Current | 6mA |
End-of-line Resistor | 200Ω + Diode |
Short Circuit Isolation | |
Total Loop Resistance | 50Ω |
Parallel Fault Resistance | 200Ω |
Continuous Current Through
Isolator (Ic Max) |
700mA |
Isolator Resistane in Closed
State (Zc Max) |
0.26Ω |
Leakage Current into Direct Short
(IL Max) |
15mA |
Voltage at which Isolator
Changes from Open to Closed (Vsc Min & Max) |
3.8V – 11V |
Voltage at which Isolator
Changes from Closed to Open (Vso Min & Max) |
3.8V – 11V |
Maximum Switching Current (Is
Max) |
1.5A |
Environmental | |
Operating Temperature | -5ºC to +45ºC |
Humidity (non condensing) | 0 to 95% RH |
Physical | |
Construction | PC / ABS / Steel |
Dimensions (H x W x D) | 300mm x 300mm x 74mm |
Weight | 5.4Kg |
Ingress Protection | IP30 |
Compatibility | |
Suitable for use with | Eaton analogue addressable fire systems (800 series protocol PR200-07-400) |
Reviews
There are no reviews yet.